Off-grid solar and battery storage calculator

Enter a daily kilowatt-hour load, how many days the batteries should last without sun, a depth of discharge, and a system voltage. You'll get the battery bank in kWh and amp-hours. Add peak sun hours for your location to size the solar array.

Battery defaults follow a Pacific Northwest National Laboratory worked example (2.293 kWh/day × 3 days ÷ 0.70 DoD = 9.8 kWh) with inverter efficiency set to 100% so that example can be reproduced. Change DoD to the PNNL Table 3 planning values (~50% lead-acid, ~85% lithium-ion) or to your battery’s rated limit. Arizona Cooperative Extension advises that a deep-cycle battery should not be discharged beyond 50% state of charge. The 96% inverter default in PVWatts is a separate, editable factor; turn it on when your load is AC. Peak sun hours are not a national average — enter the daily figure for your site from NREL’s PVWatts calculator or a solar-resource map (peak sun hours equal daily insolation in kWh/m² at 1 kW/m²). The 0.86 derate is UMD Extension’s default, cited to Dobos 2014 (PVWatts Version 5, 14% system losses). This is a planning estimate, not an engineering design.

Safety: Solar-electric and battery systems involve shock, fire, and code requirements. Use this page for planning only. Consult a licensed electrician or qualified solar installer, and follow the National Electrical Code and local permits, before you buy or wire equipment.

How battery and array size are figured

Battery capacity in kWh, following PNNL Table 7, is daily load × days of autonomy ÷ (DoD as a decimal). If you enter an inverter efficiency under 100%, the daily AC load is first divided by that efficiency so the bank is sized for the DC energy the inverter must draw. Amp-hours are kilowatt-hours × 1,000 ÷ bank voltage. Useful storage before DoD is daily load × days; the DOE fact sheet’s 1 kWh/day at 24 V is 1,000 ÷ 24 ≈ 42 amp-hours of useful storage, and a lead-acid bank must be larger than that because it cannot be fully discharged. Array size, following UMD Extension, is (daily kWh × solar offset) ÷ (peak sun hours × derate). When inverter efficiency is included, the denominator also multiplies by that efficiency, because PVWatts keeps inverter conversion out of the 14% system-loss figure. Panel count is array watts ÷ the nameplate watts you enter. Size off-grid arrays for a conservative (often winter) peak-sun-hour value, not a summer high. Arizona Extension notes a common voltage practice of 12 V for loads under 1 kWh/day, 24 V for about 1–4 kWh/day, and 48 V above that — a guideline, not a requirement.

Related guide
No matching Hands-On Homestead title yet.

FAQ

How large a battery bank do I need?

PNNL’s worked example is 2.293 kWh/day × 3 days of autonomy ÷ 0.70 depth of discharge = 9.8 kWh. At 24 V that is about 408 amp-hours of nameplate capacity. Change the days, DoD, and voltage to match your outage plan and battery type.

What depth of discharge should I use?

Use the limit on your battery’s data sheet. PNNL Table 3 lists planning values of about 50% for lead-acid and about 85% for lithium-ion. Arizona Extension says a deep-cycle battery should not be discharged beyond 50% state of charge. The 70% in the default is only the PNNL Table 7 example.

How do I find peak sun hours?

Peak sun hours are the daily solar resource expressed as hours at 1 kW/m², which is numerically the same as daily insolation in kWh/m². Look up your site in the NREL PVWatts calculator (UMD Extension walks through that). Use a winter or critical-month value for off-grid sizing, not a yearly average, if winter is when you most need the system.

Does the 14% system-loss figure include the inverter?

No. PVWatts (Dobos 2014), which UMD cites for the 86% derate, treats inverter DC-to-AC efficiency as a separate default of 96%. This tool keeps both numbers editable so you can include the inverter or set it to 100%.

Related tools

Sources: Pacific Northwest National Laboratory, PNNL-33984, An Introductory Guide to Generating, Using, and Storing Energy (April 2023), Table 7 and Table 3; U.S. Department of Energy / EERE, Battery Power for Your Residential Solar Electric System (useful Ah = watt-hours ÷ volts); University of Maryland Extension, FS-2023-0655, Working on Solar Design and System Sizing (system capacity formula; 86% derate, citing Dobos 2014); NREL, PVWatts Version 5 (14% default system losses; 96% default inverter efficiency); University of Arizona Cooperative Extension, AZ1983, Stand Alone Photovoltaic (PV) Systems (50% SOC guidance; voltage guideline). Look up peak sun hours in PVWatts. Full source list.